A building design can contain the information needed to check a regulation and still leave an architect with substantial work. An accessibility requirement may refer to usable space beside a toilet, while the design describes a plumbing fixture, its placement and the geometry of nearby objects. A fire-safety requirement may depend on building height, while the height that matters is defined using particular parts of the building. The authors develop a way to check selected requirements of this kind by giving the design data and the regulatory rules a shared vocabulary. Their examples come from regulations written in French.
The method brings together two preparations. Project participants agree on how to describe and exchange building data. The checker then converts an Industry Foundation Classes (IFC) file into a graph of facts, simplifies some geometry and derives concepts that a regulation can refer to directly. Separately, construction experts interpret the legal wording and write intermediate rules in a controlled vocabulary. Specialists turn those rules into executable SPARQL queries, which search the graph for building elements associated with violations. The system packages the findings in a format that an IFC viewer can display alongside the relevant elements. The authors implemented the checker on the French national BIM platform.
The authors applied the approach to accessibility and fire safety. Experts worked through about twelve regulatory texts and produced about one hundred intermediate constraints, adding concepts to the regulatory vocabulary as needed. The paper details a clearance check beside a toilet and a structural fire-resistance check whose threshold depends on building height. In the clearance test, the authors identify a handrail placement issue and show how an explanatory query can name the objects that intersect the clearance space. The written account leaves a consequential question about the final decision, however. The stated requirement allows clearance on either side, while the described query returns a toilet when either side is obstructed. The fire-safety example traces the calculation and lookup through to the selection of structural elements whose performance falls below the applicable threshold.
The evidence is principally about what the architecture can represent and execute. A simple example reduces a room-classification statement from at least ten graph facts to one, illustrating how repeated IFC patterns can be made easier to query. The paper gives no aggregate accuracy or timing measurements. It also gives a concrete case where simplified geometry produces the wrong result, a corridor with several aisles of different widths. What the checker can establish depends on the regulatory interpretation, the information supplied about the building and the adequacy of the geometry used for the particular check.
Deep dive: Towards French Smart Building Code: Compliance Checking Based on Semantic Rules
The paper shows how semantic rules can check French building regulations against digital designs for accessibility and fire safety. · about 32 minutes to read
The problem and its context
Why the design and the rule speak differently
Compliance checking requires a reviewer to connect a statement about what a building must provide with evidence about a particular project. The evidence may be distributed across the design. The requirement may specify an object, a location, a measurement convention and a condition that changes which limit applies. Even when each item is intelligible by itself, somebody has to decide how the pieces fit together before the check can be repeated. The paper cites an estimate that architects and construction engineers can spend up to 100 hours on compliance checking for complex projects. The figure describes the manual effort motivating the study.
A digital design gives that work a starting point. Building Information Model, or BIM, is the paper’s term for a structured digital representation of a construction project. Industry Foundation Classes, or IFC, supplies a schema that defines how building information can be organized and a file format for exchanging it. The schema is specified in the EXPRESS data description language. IFC gives a checker a consistent way to recognize many kinds of building information, but a regulatory expression can still refer to a combination of entities and properties that has no dedicated IFC term.
Consider how a design represents a building storey. A storey can have an elevation, and that information can serve several purposes in the design. A requirement that refers to the highest storey asks for an additional judgment about how storeys are related: the relevant storey is the one whose elevation makes it highest. An IFC class for storeys identifies the candidates. The regulatory expression identifies a role that depends on their relative elevations. Simply finding a term in the design vocabulary therefore gets the checker to the starting point of the judgment.
A similar distinction appears when a regulation specifies how to measure height. A search for the word height might turn up several attributes or quantities that would be plausible in ordinary conversation. In the structural fire-safety example, the relevant extent is from the ground to the floor of the highest storey. The measurement convention determines which building facts the check needs. A design that records a height somewhere can still require preparation before that quantity can be used for the regulatory decision.
Geometry adds a different kind of difficulty. A design may encode a physical object through many small surfaces. A rule concerning the intersection of two spaces frequently needs a representation that a query can compare without processing all those surfaces. Simplification can make the comparison manageable. It also changes which parts of a building the resulting geometry describes faithfully. The paper makes the choice of geometric detail part of the checking architecture because the right choice depends on what a rule asks about.
Why the regulation needs interpretation
The authors describe building regulations as documents written for human readers. Some wording permits several interpretations. Some requirements leave knowledge implicit, and statements can sometimes appear to conflict. Encoding a passage involves deciding what its terms mean, where it applies and what observations would establish a violation. These decisions call for construction expertise and for communication with the specialists who implement the checks.
That division of work matters because a query can execute faithfully while expressing the wrong interpretation. A condition may have been attached to the wrong object, or an alternative in the legal wording may have become a compulsory condition during translation. A successful execution would then show that the graph contained the pattern requested by the query. Whether that pattern corresponds to a violation is a separate question about how the rule was authored. The intermediate stage in the paper is intended to give construction experts a place to examine that question before the constraint becomes query code.
The paper situates the study in earlier work at the Centre Scientifique et Technique du Bâtiment, or CSTB. It traces work there on computerized regulation checking back to 2002 and describes an early mapping between regulatory terminology and IFC terminology. The current problem goes beyond establishing correspondences between names. A usable correspondence can require a definition that combines several facts, and the building data can come from areas described using different standards. The authors therefore seek a representation in which related facts and reusable definitions can be connected. This is an application of knowledge representation and reasoning.
The concern about different standards also places a limit on what file exchange alone can accomplish. An IFC exchange can carry a rich description of a project. Other descriptions can exist for particular building components or systems, with their own choices about how to classify things and attach properties. A checking procedure that expects a single arrangement of information can be hard to reuse even when another arrangement describes the same facts. The authors approach that issue both organizationally, by agreeing on data conventions, and technically, by bringing design information into a common form.
What earlier checking approaches offered
For verification in the buildingSMART community, the paper describes the Model View Definition, or MVD. A view specifies a subset of the IFC schema relevant to particular exchange requirements. An exchange may need particular kinds of information to be present, and the view gives participants a way to state which part of the larger schema serves that purpose. Views can be written in mvdXML, the format the paper uses in discussing earlier verification approaches.
The authors cite earlier assessments that identify restricted support for checks reaching across separate branches of an IFC representation, weak support for geometric analysis, a lack of mathematical calculations and a focus on static verification. These limitations matter to the kinds of requirements under study. A structural fire-resistance check can depend on a quantity derived from the building and then apply to a set of elements elsewhere in the data. An accessibility check can depend on the relative location of items with different functions. In both situations, the relationship among facts is part of the condition.
The paper also describes earlier attempts to express IFC as an ontology, a vocabulary that defines kinds of things and their relationships in a form software can use. Earlier transformations followed the syntax of EXPRESS closely when expressing the schema in OWL, a language for defining ontologies. The paper identifies ifcOWL as a developed version of this approach that was a buildingSMART candidate standard. With a building represented using this vocabulary, related facts can be followed as links, which provides a basis for a knowledge graph.
Moving the IFC schema into OWL brings the design data into a form that can be queried and combined with other semantic descriptions. It carries over much of the detail of the underlying schema. The paper points to prior work that simplified ifcOWL graphs and used the resulting description to check construction rules. It also cites comparisons that considered logical rules, including rules written in the Semantic Web Rule Language, as an alternative for verification tasks that strained mvdXML. These studies give the authors precedents for the use of graph queries, simplification and logical conditions.
The present paper connects that line of work to the preparation of French regulations for execution. Its design question is how to join a detailed building description, a vocabulary in which experts can express obligations and a reporting system that can tell users which elements to inspect. An ontology is the bridge between those activities. The project uses the same regulatory terms for writing constraints and for presenting selected facts about the building. That choice makes the work as much a problem of ontology engineering as a problem of running queries.
The method, step by step
Prepare the building and the rules together
The checker needs a prepared description of a project and a set of formal constraints. These inputs come from different people and at different times. The project description can change as a design develops. A regulation may be interpreted and encoded once, then checked against successive designs. The architecture gives the two sides a point of agreement in the Regulations ontology. The preparation of IFC data makes regulatory concepts available to queries. Rule authors use those same concepts when expressing what the checker is supposed to find.
From project conventions and regulations to compliance findings
The steps in order.
The first step is a modeling charter. This is an agreement among the participants in a construction project about how they will describe information and pass it to one another. It covers exchange procedures, practices for creating the digital design, export settings, agreed names and classifications. Those decisions affect what the checker can expect to find in an IFC file. A classification can be meaningful to everyone on a project and still be hard for software to retrieve if several participants encode it differently.
The charter can also specify extensions to the properties that accompany IFC objects. The paper gives certification level, equipment performance and environmental impact as examples of subjects that can need dedicated property sets. A property set groups attributes relevant to a particular purpose. Assigning a place for such attributes is important when a regulation refers to evidence that the standard exchange description does not ordinarily supply. The charter establishes where that evidence should go. Project participants must still supply the evidence about the actual elements.
The authors see project agreements as a way to reduce the variety of schemas that the checker has to handle. They also describe work towards a French national core charter that could serve as the starting point for individual projects. The intended arrangement leaves room for project choices while giving participants a common point of departure. The paper describes this national charter core as a goal being pursued in cooperation with architects, owners, engineers, specialists in auditing and quality control, and government.
Convert project information into assertions
The technical pipeline begins by converting the submitted IFC file into RDF. RDF is a representation for facts that can be organized as a graph. The basic assertion, called a triple, has a subject, a predicate and an object. The subject identifies what the fact is about. The predicate identifies the property or relation asserted. The object identifies the other thing in that relation or gives a value, such as an elevation. A triple can thus express that a given storey has a particular elevation, and other triples can connect the same storey to its building.
In the paper’s description, things and properties in the graph can be named with uniform resource identifiers, or URIs. When the object is a literal value, the predicate is a datatype property. A recorded elevation illustrates that case. When the object is another identified resource, the predicate is an object property. An assignment from an identified room to an identified category illustrates the kind of relation that uses resources at both ends. The distinction tells the query whether to expect a value to compare or another resource whose connections it can follow.
The implementation uses the Open-IFC-to-RDF-converter and applies custom filtering to the classes and relations. The resulting RDF goes into a triple store, a repository that holds the assertions and allows them to be searched together. This first conversion makes IFC information available in graph form. Additional processing is required because an IFC-derived graph can still describe the building at a level that differs from how a regulation describes it.
Both simplification and enrichment occur after or around the conversion. Some details are excluded because the authors expect little regulatory use for them. The paper names detailed geometry, histories of building elements and sensor states as examples of information that may be removed from the repository. Enrichment does the complementary work of adding facts that the queries will need. The state of the triple store at checking time is therefore a selected and interpreted view of the submitted file.
There is a practical distinction between removing detail and cutting a shorter path through it. A room classification may already be represented by a chain of relations in IFC. A direct classification assertion can make that information easier to find. Highest-storey status involves an additional determination based on elevations. It can be made available as a regulatory concept by applying a definition to facts in the building description. In either case, the query author gains a shorter expression for a fact whose preparation has been assigned to an earlier part of the system.
Give the rules a vocabulary at the right level
The authors organize the Regulations ontology in layers. ifcOWL supplies the underlying building vocabulary. A simplified representation above it gives the checker more direct ways to describe selected information. Further definitions express concepts associated with regulatory functions, properties and requirements. A concept can be defined using vocabulary at lower levels. Definitions can thus build on one another while a query at the top level refers to relatively few concepts.
This organization addresses a difference in the purpose of the vocabularies. ifcOWL provides many classes and relations closely tied to the physical description of a building. A regulatory vocabulary is concerned with what parts of a building are for, how they perform and which obligations apply to them. A regulation can speak of a structural element without enumerating the exact paths through IFC by which the checker can recognize each relevant element. Those paths belong in the definitions and the data preparation.
A useful example is room classification. In ifcOWL, the paper says it takes at least ten triples to express the relevant classification pattern. In the Regulations ontology it can be represented by one triple. The shortcut lets the checking query ask for a particular classification through a direct relationship. The remaining task is to make sure that this relationship is derived from the intended IFC pattern. The number of triples describes the representation of the classification, with no implication that the entire building graph shrinks by the same amount.
Highest storey illustrates a concept that draws on several pieces of information. The lower vocabulary provides a kind of object corresponding to an IFC building storey and a way to represent elevation. The regulation-level vocabulary provides a name for the storey identified by comparing elevations. A query concerned with fire-safety height can refer to that concept while leaving its building-specific determination to the semantic machinery. If another constraint needs the same notion of highest storey, it can use the same definition.
A toilet seat gives another example of alignment. The regulation refers to a WC in the sense of a water closet seat. The IFC description connects an IfcFlowTerminal to an IfcFlowTerminalType whose pre-defined type is WCSEAT. IfcFlowTerminal identifies the IFC category for the instance involved in that pattern. IfcFlowTerminalType provides the type information, and WCSEAT is the value used in the alignment described by the authors. The regulatory term collects those conditions into a concept the clearance query can use directly.
There is also a distinction between a regulatory concept derived from a physical part of the building and a virtual object introduced to test the design. A WC is a physical fixture that the query identifies through its description. The space beside it is represented as an object for the purposes of the check. Its presence in the reasoning means that an area of specified size and placement is under consideration. The query can relate that area to physical elements even though the designer did not model the area as something to be built.
Process the geometry that the check will use
The geometrical preprocessor is implemented in Java. It reads geometry from IFC and returns geometrical triples. The authors use bounding boxes for situations where a compact representation is adequate. A bounding box describes the extent of an object or a region through its coordinates, and the graph records those coordinates as facts. This allows geometric relationships to be checked using a much simpler description than an IFC surface representation composed of many small facets.
A box has to preserve the information that the rule depends on. In the toilet example, the direction of the fixture matters because the available space must be evaluated relative to its sides. A clearance region tied to an arbitrary direction in the building could be placed incorrectly even if it had the right dimensions. The paper therefore requires orientation for the box used in this reasoning. That condition makes the geometry of the check depend on placement and direction as well as size.
GeoSPARQL provides vocabulary for expressing topological relations between geometries. Topology here concerns how those geometries relate in space, such as whether they intersect or are adjacent. The authors use these concepts to express geometric conditions at query level. They also point to functional extensions as a way the approach could be expanded if checking called for additional computations. Which geometric representation is supplied to such a condition remains a decision about fidelity to the regulation.
The geometrical preprocessor belongs to the submitted-file pipeline. Some geometric constructions can also be made during a specific query. In the clearance example, the candidate spaces are created when the WC is checked. Each space depends on the fixture under examination, and its box can be compared with the building geometry that the preprocessing has made accessible. That division illustrates the difference between providing reusable geometric facts and constructing a test object specific to an individual rule.
Interpret each obligation and write a query
The regulatory work begins with expert groups reading and interpreting the legal material. They use editors with syntax highlighting and autocompletion when rewriting it into semi-formal rules. A semi-formal rule expresses the condition in a more regular structure and vocabulary while remaining readable to the people responsible for the regulatory interpretation. The authors propose that it name a condition on the relevant building elements and identify a violation when the condition is met.
A single legal passage may lead to several such rules. A passage can cover related obligations in close succession, making it difficult to see where one condition ends and a different check begins. Breaking it into smaller constraints lets the group examine what objects each check concerns and how it could identify a problem. The paper’s preferred unit is a rule simple enough to be understood on its own, even when several rules are needed to cover the passage from which it was derived.
Specialists familiar with BIM and Semantic Web techniques then turn the intermediate constraints into SPARQL queries. SPARQL is the query language used to search the RDF facts and identify the elements that match a condition. The formal query uses terms at the same level of the Regulations ontology as the semi-formal rule. An expert who recognizes terms for a toilet seat and clearance space has a way to follow the meaning of the query even if a specialist has to write its executable expression.
The method has a limited kind of automation at this stage. Experts supply the interpretation, the rules and suggestions for concepts that the vocabulary needs. The implementation automates the preparation of a submitted IFC file and the execution of authored checks. The paper describes no statistical training procedure. Its procedure for building the rule collection is expert analysis, explicit definition and translation, with vocabulary extensions added as the interpretation requires them.
The authors do not present a general scoring equation or a mathematical specification of the checker. The technical conditions in the examples are expressed through dimensions, geometric relations and the selection of elements by comparing properties. In the WC case the paper writes the clearance dimensions as follows.
0.8 x 1 m
Here 0.8 and 1 are the specified dimensions, x separates the two dimensions of the stated clearance, and m denotes metres. The regulation is described as allowing the clearance at the left or right side. The implementation represents each candidate space with a box that has three-dimensional extent. The stated dimensions are the values given for the requirement in the account of the example.
The fire-safety check uses a measurement from the ground to the floor of the highest storey. This requires finding the storey with the highest elevation and locating its floor, described as the lower slab of the storey. The query uses the resulting height to determine a threshold for performance in fire. It then identifies load-bearing components and retrieves the relevant performance for comparison. The level of detail the paper supplies is the sequence of these operations and the meanings of the concepts involved.
Apply semantic definitions and report findings
Submitting a new IFC file triggers the conversion and preprocessing pipeline. The semantic preprocessor applies a sequence of forward-chaining operations to prepare the regulatory view. Forward chaining starts with available building facts and uses rules to derive further facts. The new facts are stored as triples. In the architecture described by the authors, this processing happens when the data changes, so a later query can use the prepared assertions.
The paper also discusses backward chaining as an alternative. In the authors’ account, the ontology can supply statements linking IFC-level descriptions and regulatory descriptions, and the inference can be performed when a query is asked. Both strategies let the authors express how an IFC term or pattern relates to a higher-level term. Their operational distinction is the point at which the inference is carried out. The implemented preprocessor uses forward chaining to populate the repository in advance of the checks.
The regulations are grouped under topics, including fire safety, accessibility, airing and acoustics. This organization gives an architect a way to select the aspect of a design to be checked. The executable constraints are distributed as SPARQL files in a ZIP archive with metadata intended for users. The checking procedure executes the formal queries for a chosen topic individually and examines their results. Each result can therefore be associated with the particular constraint that produced it.
The reporting format is Building Collaboration Format, or BCF. It can carry a list of the elements reported for each constraint query and can be displayed in a standard IFC viewer. The viewer connects the finding to the location and identity of the element in the design. An explanatory query can supply further detail, as when it identifies the object that occupies space being checked for accessibility. That information gives the architect a concrete design relationship to inspect after receiving a finding.
Experiments and results
What the examples evaluate
The study applies the approach to selected French fire-safety and accessibility requirements. The authors adapt a first version of a regulatory ontology drawing on previous work at CSTB. A group of experts interprets about twelve regulatory texts and produces about one hundred semi-formal constraints using terms from the ontology. The vocabulary is extended with concepts suggested during this work. These quantities describe the scale of the authoring exercise. The paper does not specify exactly how many of the intermediate constraints were then implemented as executable queries.
The data in the architecture are IFC project information and the rule material interpreted by the experts. The paper presents two detailed cases, using them to show how a condition is expressed in the shared vocabulary, which building information is needed and what a query can return. It gives no named benchmark of buildings, no train or test split and no labelled collection of expected decisions. Its results support an account of implementation and representational capability. They leave error rates and the extent of coverage across projects open.
The comparison with mvdXML is qualitative. The paper considers the kinds of operations that the semantic checker supports and describes why they are useful for verification. It credits the new approach with flexible joins through the graph, the ability to extend the repository with relevant facts and access to a wider range of query operations. The conclusion also recognizes the cost in time of the initial conversion to RDF. The paper supplies no paired run of the two approaches with recorded runtimes, memory use or compliance decisions.
There is a numerical comparison for the size of a particular representation. The room-classification illustration contrasts the number of triples used by the ifcOWL pattern with the number used by the shortcut in the Regulations ontology. This is a count for one classification assertion. The ifcOWL value is a reported lower bound, while the Regulations ontology provides a direct assertion.
Triple count for the paper’s room-classification example
The Regulations ontology expresses the classification with a direct assertion.
The numbers
| System or setting | triples per classification |
|---|---|
| ifcOWL pattern, reported minimum | 10 |
| Regulations ontology shortcut (this paper) | 1 |
The metric isolates why the shortcut is convenient for a query writer. A classification described through a chain has to be reached through that chain or through an equivalent query pattern. A direct relationship can be requested immediately once it has been prepared. This example measures the length of a representation. The total graph size, the work of deriving the shortcut and the time a real query saves would require measurements at other levels.
Accessibility around a toilet seat
The accessibility example starts with a rule requiring a free space of 0.8 x 1 m to the left or to the right of a WC seat. The regulatory vocabulary lets the query find WCs without spelling out the IFC typing pattern in the check itself. The query constructs candidate spaces beside the fixture, with a space on each side and a bounding box for each. The positions depend on the WC’s orientation. The next operation identifies physical building elements that intersect each candidate space.
The paper gives two descriptions of what should happen at the final selection step, with different implications. Its statement of the regulation allows the required clearance on either side. If a physical element occupies one candidate space and the other is clear, the clear side can fulfill the requirement as stated. The algorithm described in the paper returns a WC when at least one candidate space intersects a building element. In that same situation, the reported selection condition would include the WC. The difference matters because the returned elements are described as violations.
The two descriptions agree in the cases where both spaces are clear or both are obstructed. They diverge where the results for the sides differ. The paper supplies no separate treatment of that case that establishes how the implementation resolves it. One can therefore follow the demonstrated procedure for constructing clearance spaces and retrieving obstructions while leaving the correctness of the final compliance decision unsettled. This issue concerns the logic combining the results for the sides. The intersection operation can produce the intended result for each individual space even if the rule combines those results incorrectly.
A query for explanation can identify the physical items that intersect a clearance space. The authors report detecting a problem involving the placement of a handrail in their test. This is a concrete result about what the check brought to attention, and the explanation shows how the output can point someone to the relevant geometry. The paper does not give a count of all WCs examined, report whether each had qualifying clearance on its other side or compare the query’s decisions against an independent review. The handrail finding establishes that the query can surface a placement issue without settling how the cases were classified overall.
The use of bounding boxes is also a result specific to this example. The authors found the representation sufficiently accurate for detecting the clashes considered here, provided the orientation let the system tell left from right. The relevant result is that a simple geometry sufficed for the stated test. Whether another arrangement could cause a box to include space outside the fixture depends on the shape and on what the particular rule needs to measure.
Fire resistance of load-bearing elements
The fire-safety example concerns how long load-bearing elements must continue to support loads if a fire occurs. The authors mention a requirement of at least one hour and explain that the threshold varies with the height of the building. The check accordingly needs both a performance value for the relevant elements and a way to choose the applicable threshold. It obtains the latter from the height defined for this regulatory purpose.
The query first calculates height using the ground and the floor of the highest storey. To get that floor it needs the high-level notion of the highest storey and the definition of a storey floor as the lower slab. Next it determines the performance threshold corresponding to the height. It retrieves the structural elements, identifies their fire-resistance performance and returns elements below that threshold. The comparison therefore depends on a building-level result and is applied to properties of individual elements.
Several decisions that a reviewer might make in a manual check become explicit in this example. The height has specific endpoints. The elements to be checked are the parts that bear loads. The property concerns continued support in a fire. The applicable comparison depends on the building’s measured height. Keeping these parts visible helps explain why a single field in the original file is insufficient to express the whole rule and how the query assembles the required facts.
The paper gives the direction of the comparison and the kind of element the check returns. It gives no measured building height, complete schedule of thresholds or list of structural elements returned in a particular submission. The one-hour figure refers to fire performance in the regulatory example. It supplies neither a measured fire-resistance result for a design nor a threshold shown to hold across all building heights.
Together, the cases show that different kinds of constraints can use the same preparation and reporting mechanism. The clearance query constructs space and relates it to physical geometry. The fire query derives a quantity, uses it to select a threshold and compares element properties with that threshold. The paper reports that the implementation on the French national BIM platform automated checking on various topics in these areas. Its examples give substance to that claim by tracing concrete queries through the architecture, with no aggregate counts of correct or incorrect results.
What the ablations show
The paper reports no controlled ablation study. Its analyses instead compare representations and verification capabilities, discuss when semantic inference is performed and use geometric examples to identify conditions under which a simplification is adequate. They help explain what each part of the architecture is intended to accomplish. They leave open the size of its contribution to the performance or correctness of the overall checker.
How the representation changes the query
The room-classification comparison comes closest to isolating a local change. The information being requested is a room’s classification. The ifcOWL representation encodes it through a pattern of facts, while the Regulations ontology makes it accessible through a direct relation. The authors make that difference visible by counting the facts in each representation. The result explains how a shorter query expression becomes possible once the repository contains the shortcut.
This comparison leaves work on the preparation side. To obtain the shortcut, the system must identify correctly the IFC relationships that express the classification. If a project uses a different convention, the checker’s ability to produce the direct relation depends on its agreement with that convention or on suitable alignment. The authors’ modeling charter and semantic preprocessor address those issues in different ways. The charter helps constrain the ways the information is supplied. The preprocessor carries out the relevant interpretation of information that has been supplied.
The paper’s comparison with mvdXML addresses a broader question. It claims that the semantic system can express operations needed for a wider range of checks, with the graph supplying connections across the building information and preprocessing supplying useful derived facts. The examples make those operations concrete, from geometric intersection to a calculation used to select a threshold. The paper does not report a version of either example executed using mvdXML under the same conditions. The comparison explains the authors’ technical motivation and claimed capabilities.
When it is useful to perform inference
The forward- and backward-chaining discussion compares strategies for exposing regulatory concepts to queries. Under forward chaining, a change to the supplied data triggers inference and produces supplementary assertions. Under backward chaining, the relevant ontology statements are used to infer what is needed when a query is issued. In either case, a rule writer can refer to a concept whose meaning is defined using IFC-level information.
The authors regard backward chaining through ontology statements as attractive in principle and describe forward chaining as an optimization that can save memory and CPU resources. Their discussion provides the timing distinction on which the optimization rests. If several queries need a concept, a previously derived assertion can be reused when those queries run. If the data changes, the assertions must reflect the changed information. The scheduling of computation is therefore relevant both at submission time and while a user is running checks.
There are no CPU measurements, memory measurements or query timings attached to the comparison. The paper also omits a workload description that would tell the reader how many queries usually reuse a derived concept or how often the underlying data changes. The evidence supports the location of inference in the implemented pipeline and the authors’ explanation of why they chose it. The amount of saving, and its dependence on a given workload, remains unmeasured in the paper.
What the geometry examples establish
The clearance case and the corridor discussed in the conclusion indicate when a geometric simplification can affect a result. In the WC example, the authors found that boxes served the clash investigation and singled out the importance of orientation. A query needs the geometry to distinguish spaces tied to a fixture’s left and right. In the corridor example, a box can mask the varying widths of the aisles and lead to erroneous intersection results.
The cases involve different geometries and do not constitute an experiment that holds the project and rule constant while substituting another geometric representation. Their contribution is to show the dependency of the result on which information survives simplification. A relation like intersection may be computed as intended for the shapes in the repository. To support the regulatory conclusion, those shapes also have to represent the parts of the building implicated in the rule.
The discrepancy in the clearance rule points to a separate dependency. Here the description allows the reader to inspect whether the query’s conclusions follow from its per-side findings. Detecting an obstacle and deciding that the WC violates the rule are distinct operations. An account of the obstacle can be valid even when the selection condition fails to preserve the alternative given in the requirement. The paper’s examples consequently make it possible to scrutinize both the geometric evidence and the way the query uses that evidence.
Limitations
Limits identified by the authors
The authors explicitly limit the scope of the architecture to a portion of the obligations found in regulations. Their geometric counterexample is a complex corridor with multiple aisles and differing widths. A box can include areas that do not correspond to the shape available for movement. If the checker tests intersections involving that box, some conclusions can be erroneous. The example qualifies the authors’ broader observation that many of the geometrical constraints they examined could be handled without the full geometric description.
The paper also identifies missing information. Certain properties specific to national regulations have to be added to IFC-based project descriptions. Directions of door opening provide an example of a check that can depend on the fire escape plan, which the authors identify as outside the scope of IFC. A design may describe the door and its opening geometry faithfully. The check still needs the plan to determine the context in which that opening is to be evaluated. The regulation vocabulary can express the need for those facts, while the facts must come from a source that contains them.
The authors observe that many constraints they encountered involve retrieving elements and checking their properties. They also identify intersection and adjacency as frequent spatial relations. These observations help explain the practical starting point for the implementation. They leave a range of requirements that can call for additional geometric operations, external information or interpretations that cannot readily be captured in that pattern. The authors propose geometric functional extensions in cases that need them and identify related ontology work as a possible basis for further development.
Preparing a semantic repository also takes time. The paper recognizes the IFC-to-RDF transformation as an overhead incurred before the checking queries can exploit the graph. The authors judge that the prepared repository is easier to explore and extend. The paper gives no timing evidence to show how preparation and repeated use balance for projects of different sizes or at different rates of resubmission. Its implementation claim and its account of efficiency therefore have different levels of support.
Limits visible from the setup
The study’s strongest evidence comes from the details of particular procedures. It has no published set of expected compliance decisions against which to measure the output, and it reports no aggregate accuracy, false findings or missed violations. The number of authored intermediate constraints gives a sense of the effort invested in interpreting the regulations. It does not give the fraction of applicable requirements that the checker covered or the proportion of correct decisions on actual submissions. Those quantities use different units and require different evidence.
The authors describe construction experts and technical specialists cooperating on the translation. The publication gives no comparison of independent interpretations of the same text or measurement of agreement among the experts. The semi-formal stage provides a place to make choices visible, but the quality of the resulting conditions depends on the decisions made there and on how they are carried into the query. The clearance example shows why this is consequential. A check that reports a violation after finding any obstruction has different meaning from a check in which either unobstructed side is sufficient. The account leaves that difference unresolved.
A result also depends on data having arrived in the expected form. A missing performance property, for instance, poses a different issue from a property whose value is below a threshold. A rule that searches for a recorded value below the limit can return a list of those cases. A reader also needs to know whether unrecorded values produce a separate finding, prevent the evaluation or pass silently through that particular query. The paper does not define how such situations are handled across the checker. An empty result is therefore evidence about matching query conditions in the prepared graph, with its significance depending on data completeness and the rule’s coverage.
The account of schema heterogeneity identifies the need to accommodate differences among descriptions of building information. The implemented chain is explained in terms of IFC submissions. The paper does not present a cross-schema evaluation showing that independently structured descriptions of the same building produce equivalent results. Modeling agreements and a shared vocabulary are mechanisms for improving interoperability. The extent to which those mechanisms carry over across standards, export practices and projects would have to be assessed with those varied inputs.
There are also limits on what can be inferred from the figure for room-classification triples. The count illustrates a local improvement in the form used by queries. It leaves the sizes of full repositories and the costs of preprocessing and maintenance unmeasured. Inference can add facts at the same time as filtering removes others. A short path in the final vocabulary and a smaller overall repository are different outcomes, and the paper measures neither overall repository size nor the effect of the shortcut on execution time.
Finally, the report identifies a practical endpoint for the prototype: findings can be tied to building elements and inspected in an IFC viewer. This makes the result actionable for a reviewer and helps expose the basis of some checks, as with the obstruction query. The paper does not evaluate how reviewers use these reports, how much time they save or whether they find the explanations sufficient to resolve disagreements. Its motivating estimate of up to 100 hours concerns manual work on complex projects. The study supplies no estimate of the time recovered by deploying the checker.
What came after
The paper ends with plans for extending the architecture through work on linked building data. It identifies the Building Topology Ontology, or BOT, as a vocabulary for core building concepts from the W3C Linked Building Data Community Group. The direction is relevant to the paper’s use of a simplified layer above the detailed IFC vocabulary. A common description of basic building concepts could give rule authors a shared foundation for their more specialized regulatory definitions. The paper presents that as a prospective extension and does not report a BOT-based implementation.
The authors also point to OntoBREP, an ontology for computer-aided design data and geometric constraints. This direction addresses the geometry available to queries. The checker already distinguishes among regulatory concepts, physical geometry and spaces constructed for a test. More expressive geometry is pertinent to the situations for which the authors find bounding boxes inadequate. The paper identifies related work that could inform an extension, with the integration and its effect on checking left open.
These are directions the authors identify for subsequent development. No subsequent study is documented here that implements the proposed integrations or measures their effect on the checker. The demonstrated implementation uses the IFC-derived graph, the Regulations ontology, geometry preparation and topic-specific queries. BOT and OntoBREP mark the two parts of that architecture the authors saw scope to extend, the shared building vocabulary and the representation of geometric constraints.
Cite
Cite as Nicolas Bus, Ana Roxin, Guillaume Picinbono and Muhammad Fahad. 2019. Towards French Smart Building Code: Compliance Checking Based on Semantic Rules. arXiv:1910.00334 · Linked Data for Architecture and Construction (LDAC'2018), Jun 2018, Londres, United Kingdom.
@misc{bus2019french,
title = {{Towards French Smart Building Code: Compliance Checking Based on Semantic Rules}},